30 kVA Diesel Generator manufacturers and suppliers

DG Set with Volvo Eicher Engine



Specifications :


PARAMETERS DG MODELS
Duty (Standby/ Prime) Prime Stand By
50 HZ PRIME Rating(kVA) 30 kVA 30 kVA
Rated(kWe) 24 24
Engine Model 3445TCIGM-C2 3385 ELSTCGMC2
No of Phases 1/3 1/3
No of Cylinders 3 3
Output Voltage (V) 230V/415V 230V/415V
Current (A) (1Phase / 3Phase) 130.4 / 41.7 130.4 / 41.7
Power Factor (lagging) 0.8 0.8
Frequency (Hz)/ RPM 50/1500 50/1500
Governing class A1 A1
Starting system 12 V DC Elec 12 V DC Elec
Fuel Tank Capacity (lits) 115 115
Genset Dimension (LxWxH $$) (mm) Approx. 3 Phase: 2000x980x1280
1 Phase: 2200x980x1280
3 Phase: 2000x980x1280
1 Phase: 2200x980x1280
Genset Weight (Kg), Appx 3 Phase: 935
1 Phase: 1026
3 Phase: 935
1 Phase: 1026
Make Mahindra Mahindra
Power Output# (HP) 44 38.6
Aspiration Turbocharged & Intercooled Turbocharged
No of Cylinders 3 3
Bore x Stroke (mm) 88.9 x 110 88.9 x 120
Displacement (cc) 2048 2235
Fuel consumption @ 75% load (lit/hr) ^ 5.7 -
Fuel consumption @ 100% load (lit/hr) ^ 7.3 -
Lube oil specification SAE15W40 CI4 SAE15W40 CI4
Total Lube Oil capacity (lit) 7 7
Lube Oil Consumption (lit/hr) $ 0.15% of Fuel Consumption 0.15% of Fuel Consumption
Lube oil change period (hrs.) 300 hrs. for Oil Top Up
600 hrs. for Oil change
300 hrs. for Oil Top Up
600 hrs. for Oil change
Radiator coolant capacity (liter) 9.5 9.5
Alternator
Make CG/LS
Enclosure Type IP23
Voltage regulation ±1%
Class of insulation Class H
Maximum Unbalanced Load across Phases 25%